Go to homepage
Your account
Log in
or sign up
Overview Your profile Addresses Payment methods Orders
€0.00*
Home
NH Fuses
NH Fusegear
European Square Body Fuses
Medium Voltage Fuses
Semiconductor Fuses
Semiconductor Fuses (GSGB series)
British Low Voltage Fuses
British Low Voltage Fusegear
Cylindrical Fuses
Cylindrical Fusegear
D&D0 Fuses
Round Body Fuses
Traction Fuses
Telpower Fuses
Special Fuses
NATO and Military Fuses
Show all categories RedSpot Fuse Holders Maintenance Back
  • Show RedSpot Fuse Holders Maintenance
  • NH Fuses
  • NH Fusegear
  • European Square Body Fuses
  • Medium Voltage Fuses
  • Semiconductor Fuses
  • Semiconductor Fuses (GSGB series)
  • British Low Voltage Fuses
  • British Low Voltage Fusegear
  • Cylindrical Fuses
  • Cylindrical Fusegear
  • D&D0 Fuses
  • Round Body Fuses
  • Traction Fuses
  • Telpower Fuses
  • Special Fuses
  • NATO and Military Fuses
  1. Footer Bussmann
  2. RedSpot Fuse Holders Maintenance
RED SPOT 20A BACK STUD CONNECTED BLACK RS20P-G
Fuse base, low voltage, 20 A, AC 690 V, BS88/A1, 1P, BS, back stud connected, black

€26.49*
RED SPOT-ACCESSORIES PADLOCKABLE INSERTS
RED SPOT-ACCESSORIES PADLOCKABLE INSERTS RS20LOCK
Padlockable inserts, low voltage, 20 A, BS88/A1, BS

€19.35*
RED SPOT-ACCESSORIES WARNING CARRIERS
RED SPOT-ACCESSORIES WARNING CARRIERS RS32RED
Fuse base, low voltage, 32 A, AC 690 V, BS88/A2, 1P, BS

€29.66*

Method of cabling

Front connected fuse holders

  • Remove Red nylon insulating shroud to release cable sleeve.
  • Remove cable sleeve.
  • Fit cable sleeve over cable.
  • Fit conductor into fuse base terminal and tighten cable clamping screw to secure.
  • Replace Red nylon shroud taking care it holds the cable sleeve in position by locating the shroud in the groove provided by the sleeves.

Cable selection and termination

  • Ensure cable sizes are correctly chosen in line with the IEE Wiring Regulations (BS 7671), making due allowance for:
i. Grouping of cables (correction factor Cg).
ii. Ambient temperature / internal enclosure temperature (correction factor Ca).
  • Ensure that maximum cable core temperature is restricted to 70°C or less.
  • Ensure adequate cable length is provided for interconnections between fuse holders or other components. This will prevent possible heat input to the fuse holder which could result in overheating.
  • If using multi-stranded cables / Tri-rated cables the bared strands should be crimped in thin wall copper ferrules in order to consolidate the strands. The following points should be taken into account:
i. The inside diameter of the ferrules should match that of bared cable ends.
ii. The ferrule lengths should be the same length as the cable entry tunnel in the fuse base terminals.
iii. The termination screw should compress the wall of the ferrules, providing further consolidation of the cable strands within the ferrule.
  • When used in banks, ensure that the diversity factors recommended in BS5486 Part 11, Factory Built Assemblies, are applied. If the number of fuse holders banked together exceeds 12 a 0.6 diversity factor may be used.
  • For applications when there is insufficient or no diversity applied, adequate compensation should be made by a combination of some, or all, of the following:

i. Utilise higher standard current rated fuse links, or motor rated fuse links.
ii. Increase the cable size.
iii. Ensure that fuse holders in the bank are separated by at least 5mm.
iv. Ensure that there is adequate spacing between fuse banks if they are stacked vertically. Typically, depending on rating, this would be 30-50mm.
v. Incorporate natural or forced ventilation.

These measures should ensure that the heat is adequately exported
from the fuses.

  • Sharp bends in cables, especially near termination points, should be avoided in order to prevent damage to cable cores or insulation and to ensure that no mechanical strain, is put on the contact block in the fuse
    base.
  • The minimum torque values detailed in the attached table should be applied to cable terminal and fuse link fixing screws.

 

 

Important note:
These products should be installed, commissioned and maintained by, or under the supervision of, a competent person, in accordance with current Electricity at Work Regulations, IEE Regulations for the Electrical Equipment of buildings, Statutory requirements and any other specific instructions issued by GE Power Controls Ltd. These notes assume throughout that the product is isolated from the supply during installation or maintenance. It is essential that this is done before commencement of any work. Any covers, or other safety measures which are removed during installation or maintenance must be replaced on completion.

(Information from Red Spot catalogue.)

Service hotline

Support and counselling via: sales888@casadaa.com +49202702031 Monday-Friday, 10 am - 4 pm CE(S)T.

Or via our contact form.
Service
  • About Us
  • Imprint
  • Privacy
  • Terms and Conditions for Consumers
  • Terms and Conditions for Businesses
  • Export Customers
Links
  • Company Website
  • LinkedIn
  • Facebook
  • Instagram
  • Youtube
Casadaa Distribution Stores for Business
  • Eaton Bussmann Fuse Store: Fuses.eu
  • Lawson Fuses Ltd. Store: BS88.eu
  • Relays Store: RelayGo.es
  • Eaton Moeller series Store: LWD24.com
  • Waermewandler.info
Casadaaa Services for Business
  • Casadaa Personalvermittlung
Footer Bussmann
  • Bussmann Fuses by Casaadaa
  • RedSpot Fuse Holders Maintenance
  • RedSpot Fuse Link Selection

    * All prices excl. VAT plus shipping costs and possible delivery charges, if not stated otherwise.

    This website uses cookies to ensure the best experience possible. More information...